|
Conference Papers | 2005 Victorian Conference Papers
ADWG
COMPLIANCE IN REGIONAL VICTORIA
Chris
Speight, Technical
Director,
AQ2 Limited, www.smartaflow.com
Maureen Mawson, Marketing
Manager,
AQ2 Limited
Richard Ball, Marketing
and Sales Director,
AQ2 Limited
DOWNLOAD
(pdf
70 KB)
ABSTRACT
The
introduction of the Australian Drinking Water Guidelines
(ADWG) is posing a substantial challenge to water corporations
to provide safe drinking water to all citizens. Of particular
concern are regional network supply systems, delivering
drinking water to small rural communities. Traditionally,
water corporations have used chlorine gas for disinfection
at the source of the network yet this method can have
limitations in carrying through to the extremities.
This paper presents the results of a trial by Coliban
Water of a novel water disinfection technology (Smartaflow)
that enables micro-dosing for a remote community in
Victoria (Bealiba). The technology described automatically
meters sodium hypochlorite into a pressurised water
stream in a way that overcomes the limitations of traditional
systems. Despite challenging conditions, the results
of the trial demonstrate the capability of the technology
to safely and reliably dose the water within acceptable
residual levels and to provide significant benefits
in health and safety and in monitoring and management.
KEY
WORDS
ADWG,
Water Disinfection, Hypochlorination, Drinking Water,
Remote Communities
1.0 INTRODUCTION
In July 2004, the Victorian State Government introduced
legislative changes to the Safe Drinking Water Act (2003).
A key component of the act, which was adapted from the
national Australian Drinking Water Guideline Standards
(ADWG), was the need for water providers to meet strict
standards relating to the safe disinfection of drinking
water. This component of the legislation is likely to
impact on regional network supply systems, particularly
those delivering drinking water to small rural communities.
Prior to the act, it was considered acceptable to treat
a network of these localities with a single disinfection
unit. Traditionally, this broad application technique
would use chlorine gas (Cl2), at the source of the network,
dosed at a rate capable of carrying the chlorine through
to the extremities of the network.
There are a number of irregularities that this type
of chlorination creates, such as:
- the
potential to over-chlorinate at source of system resulting
in taste and odour problems, contravention of the
ADWG standards and risk to public health,
- the
potential to under-chlorinate at extremities of system
resulting in irregular chlorine residual levels, non-compliance
with ADWG standards and severe risk to public health,
-
stringent regulations associated with the potential
hazards of chlorine gas, requiring expensive safety/security
infrastructure and the need for checks by skilled
personnel.
Given these issues and the need to meet the new standards,
many Victorian regional water utilities are being challenged
as to how to improve the rural network disinfection
process.
Considering
that regional Victoria is made up of more than 212 urban
localities where populations of less than 1,000 dwell
within a network of small (often remote) townships and
communities, enormous challenges are emerging for water
utilities to be able to provide safe drinking water
for all citizens.
This challenge is not unique to Victoria, or even Australia.
The World Health Organisation's (WHO) "Guidelines for
Drinking-water Quality" have become the international
reference point for standard setting and drinking water
safety and are being adopted by countries throughout
the world. In the US alone it is estimated that there
are 165,471 public drinking water systems, 82% of which
supply populations of 500 or less1, all of which must
comply with standards regulated by the US Safe Drinking
Water Act.
Suppliers of urban potable water, driven by these exacting
standards also have serious issues with regard to how
to chlorinate (or re-chlorinate) in a safe, reliable
and economical way. This is particularly the case in
variable flow scenarios where the treatable reticulation
system is downstream of the treatment plant. Ideally,
chlorination of this type is far better administered
into a fixed flow scenario - disinfection taking place
using the fixed flow replenishment cycle of a summit
tank, or similar. In such cases chlorination takes place
on the tank inflow and the town reticulation is gravity
fed via the outflow of the tank. In this scenario an
acceptable minimum flow rate (> 1 L/s) can easily be
obtained, enabling conventional chlorination to be used
with acceptable effect. Unfortunately, this is often
neither a practical nor a viable alternative for suppliers
and variable flow chlorination is the only option. Therefore,
in cases where flows drop below 1 L/s conventional chlorination
is not possible.

Figure 1: Typical weekly winter
flow pattern of a small town water supply
Typical variable flow patterns experienced in small
town water supplies are often far lower than what would
have been previously thought. Research undertaken during
a typical winter flow pattern in the Western Australian
town of Ballidu in June 2002 is shown in Figure 1. This
shows that the flow into the town reticulation failed
to achieve a flow greater than 0.2 L/s for more than
50% of the week. This has been found to be a common
scenario throughout WA rural townships with similar
demographics.
The
chlorination of a town water supply with variable flows
of this nature, commonly referred to as micro-flows,
is the primary focus of this paper. The paper outlines
the implementation of an alternative, patented, disinfection
technology developed by the WA company, AQ2 Ltd.
The
Smartaflow technology is capable of dosing precise amounts
of disinfection agent into variable and sometimes near
zero flows. This technology has enabled one Victorian
rural water utility, Coliban Water, to retain its existing
gas chlorination system for primary disinfection at
the source of a major water distribution network with
the new technology playing a secondary role for disinfection
at the point of use, as and when required. The technique
not only ensures that network extremities - in this
case a remote rural township, Bealiba, with a population
less than 100 - always conforms to the ADWG standards,
but it will also lead to a reduction in primary chlorination
in the longer term.
2.0
THE SMARTAFLOW TECHNOLOGY
Coliban Water was aiming to achieve 100% ADWG compliance
for Bealiba, located at the extremities of the Laanecoorie
water distribution system, situated in the Goldfields
region of Central Victoria. As conventional disinfection
technologies were considered impractical and not viable
for regional ("micro") water supply systems, alternative
technologies were sought. The Smartaflow Chlorisafe
system has already been extensively trialled and implemented
in a number of locations throughout regional WA. Commonly
referred to as a "hypochlorinator", the turnkey-packaged
Smartaflow unit automatically meters sodium hypochlorite
(NaOCl) into a pressurised water stream and overcomes
the vapour lock problem that has long been associated
with traditional hypochlorite dosing technologies. The
Smartaflow Chlorisafe system is illustrated in Figure
2.

Figure 2: The Smartaflow Chlorisafe System
The Smartaflow Chlorisafe system provides a number of
distinct benefits:
Safety - unsafe work practices, such as manual
decanting, are eliminated and operators are not exposed
to chemical hazards. Removes/reduces reliance on gaseous
chlorine, eliminating risks associated with the transport,
handling, storage and application of chlorine gas.
Versatility - can be used on all types of water
in any location, adaptable to any type of chemical container
and can be used in any industry requiring precise, effective
and safe dosing of hazardous or other chemicals.
Cost
effectiveness - doesn't need extensive supporting
infrastructure or buffer zones. Uses negligible power
and costs less than a third of an equivalent gaseous
system to install. Maintainable by a single operator
and monitored remotely, reducing site attendance and
maximising operator efficiency. Auto-decant system reduces
chemical wastage.
Accuracy
- turndown ratio is 20 times higher than conventional
pumps and far greater than chlorine gas systems. Controller
ensures accurate dosing at all times, under all field
and chemical conditions, with a range of control regimes.
Reliability
- Highly reliable system. Signal sent to the operator
or central control point well before chemical replenishment
is required ensures system never runs out of liquid.
Battery backup ensures non-stop dosing, even with loss
of power. Independently bench and field-tested, the
system has been proven to be reliable even in extreme
operating conditions.
3.0
SMARTAFLOW TRIAL BY COLIBAN WATER
To
help with the introduction of the new technology into
Victoria, Coliban Water undertook a comprehensive trial
of the Smartaflow system. The main objectives of the
trial were to demonstrate the Smartaflow system's capabilities
in particular to: (i) overcoming the vapour lock problems
associated with traditional hypochlorite dosing technologies,
(ii) overcoming Occupational Health and Safety (OHS)
issues in handling the chemical, (iii) overcoming the
need for mains power, and (iv) providing dial-out and
dial-in access for remote monitoring.
The trials of the Smartaflow unit in Victoria commenced
in October 2004, using the standard purpose-built PLC
based Smartaflow controller. The controller uses a conventional
flow pace/ residual trim loop program and, in order
to accommodate the micro-dosing capabilities of the
pump, a special algorithm has been formulated. By using
a combination of the conventional proportional derivative
(in the form of variable pulse frequency proportional
to flow), in conjunction with a novel by-pass auto positioning
method, the desired turndown is achieved.
The
successful metering of micro amounts of full strength
hypochlorite solution in water flows as low as 0.02
L/s (or zero) to above 15 L/s (at peak), creates a need
for a specialised method of infusion. In order to facilitate
acceptable dilution, particularly under low velocity
conditions, a novel type of injection spear - the SpearSafe,
incorporating an inbuilt pressure sustaining device
at its tip, is also used. The successful use of this
combination of devices and control methods enables set-point
disinfection to be achieved under all seasonal conditions.
Early operation of the system at Bealiba showed the
need for the replacement of the original chlorine residual
analyser in order to cope with greater than expected
fluctuations in pH. It was also recognised that, due
to the drought, there were increasing occurrences of
higher than anticipated flows into the Bealiba town
site. Particularly prevalent during the early summer
months, there were many instances of flow "spikes" in
excess of the anticipated peak of 3.5 L/s, thought to
be caused by water carting from either of the town's
two agricultural stand pipes.
A third issue though was the hydraulic design. The first
design plan had been to locate the system adjacent to
the Bealiba 500m3 reservoir, approximately 3 km upstream
of the town site. This positioning was based on the
idea that the chlorination would take place using the
standard variable flow pace control regime with residual
trim on the outflow of the tank. As already described,
this is a very difficult method of reliably disinfecting
to within a set residual. The original design was to
divert the tank outlet via a side stream arrangement,
in association with a vertically orientated looped manifold,
situated directly above the metering pumps (within the
hypochlorinator cabinet).
The
purpose of the vertical loop was to facilitate "upward
discharging" to eliminate potential pump discharge vapour
lock. Under normal conditions, this would have not been
required, but given the likelihood of prolonged micro-flow
conditions during dormant winter periods, it was considered
essential. However, due to the fact that the treatable
water levels in the reservoir were sometimes dropping
below the highest point of the manifold, there were
occasions, during these abnormally high flow conditions,
when the system would malfunction. High flows created
within the manifold resulted in a reverse siphon effect
within the residual analyser sample cell, causing air
to be drawn into the manifold via the residual analyser
cell drain line from atmosphere.
To remedy this, the vertical loop needed to be removed.
However, the potential for downward discharge problems
were then of concern. If the manifold was to be lowered,
then there was the likelihood that "downward discharging"
could result in a vapour lock condition. As a safeguard,
the "auto purge" facility, which initiates a pre-self-bleed
regime immediately before the stand-by pump assumes
duty, was successfully adopted. The introduction of
this self-bleed function ensured that if a duty pump
failed to maintain a pre-determined minimum chlorine
residual it would initiate the auto-purge function.
Table 1: Site Conditions of
Bealiba Trial

Whilst the adverse conditions at the site, summarised
in Table 1, did create unusual challenges, the modifications
were effective, allowing extremely precise dosing and
set-point maintenance even at zero flows. The performance
of the system was monitored over two 3-month periods,
October to December 2004 and January to March 2005.
4.0 RESULTS OF THE TRIAL
As already mentioned, the combination of auto bypass,
specialised software and a unique method of injection
has proved to be particularly effective in enabling
swift switching between flow ranges, resulting in a
far higher degree of turndown than that of any conventional
metering pumping system. This facility is particularly
useful at this site, where a combination of broad flow
ranges (a consequence of seasonal water carting for
agricultural purposes) and the varying incidence of
ammonia-N, creates a need for a responsive turn down
that caters for almost all conditions.
4.1
Dose Rate Control
It
is important to note that there are two known exceptions
where control is unable to respond within a sufficient
timeframe. Referred to as a disruption period, during
these times flows become unusually erratic. Invariably
these disruption periods tend to be for short periods
of time, resulting in the residual trends going outside
the acceptable band and can be categorised into two
types of conditions:
Transitional
- these are regular occurrences specific to small town
water supplies, where the flow rate fluctuates in an
erratic manner as it enters into and out of the dormancy
period.
Flow spikes - a condition where high flows,
likely to be initiated by the use of agricultural water
supply stand pipes (or similar) occur for short periods
of time.
In both of these cases, the duration tends to be less
than 30 minutes, inevitably causing the residual to
initially rise, resulting in the duty metering pump
to go out of bounds as the pre-set threshold is exceeded.
This in turn causes the metering pump to turn off (pump-off)
and the pump only resumes operation once residual falls
bellow a pre-determined point where the pump turns on
again (pump-on). However, given that we know these periods
tend to be short lived, it has become possible to manage
these disruption periods, rather than trying to effect
control as they are taking place. To do this, a dose-rate
suppression method is used.

Figure 3: Comparison Diagram
On The Effects Of Dose Rate Suppression
As already mentioned, a specially formulated algorithm
had to be developed to manage control of pulse rate
- proportional to water flow, whilst at the same time
determining the chemical volume per pulse by varying
the auto by-pass. Because these disruption periods tend
to be limited in duration and occur infrequently, by
suppressing the auto by-pass activity in favour of pulse
rate control, it was found that control during these
periods became far more manageable. This is evident
in Figure 3 where the dose rate in trend 1 is suppressed,
ensuring that the auto by-pass remains constant for
much longer than it does in trend 2.
Therefore,
it has been determined that in cases where disruption
periods occur, it is acceptable to allow the residual
trends to exceed the limits, as long as the dose rate
suppression method is used to minimise the effects.
In cases where flow spikes become more frequent as a
consequence of increased agricultural stand pipe use,
it would be far more advisable to consider engineering-out
the community based facility - by the use of a dispensing
tank with a restricted inflow, rather than attempting
to change the residual control methods used.
4.2
Performance
The performance is well illustrated in Figures 4 and
5, clearly showing the chlorine residual and flow rate
as a function of time of day during two opposing seasonal
conditions - winter and summer at Bealiba. It is evident
that even at near zero flow conditions, the Smartaflow
unit was able to maintain an appropriate chlorine residual
within the required limits.
The
manner in which the charts, each representing a 24-hour
period (8:00 am to 8:00 pm), are presented, are described
as follows:
1) Flow rate: a linear (blue) depiction, presenting
10 minute averages of the instantaneous flow rate throughout
the period, as measured using the ABB magnetic flow
meter. The chart depicts the rate in litres per second,
using a zero to 6 litres per second flow range
2)
Residual: a linear (red) depiction presenting
10 minute average of total chlorine residual as measured
using a Trent Micro-Chem analyser, sampling continuously
down stream (within three metres of the point of injection),
having a lag time of 4 minutes duration and using a
zero to 3mg per litre residual range.

Figure 4: Chlorine Residuals
and Flow Rates - Summer Flow
3) By pass: a linear (black) depiction presenting
movement in the position of the duty pump's auto positioner,
utilising the zero to 1 flow range axis, where 1 = 1000
ohms (by-pass fully open)
4)
Residual Hi: An arrowed marker (Lilac) depicting
the precise time (within 10 minutes) where the chlorine
trend went higher than is normally acceptable - referred
to as the disruption period. This condition (already
described - Dose Rate Control), refers to the instances
where the residual trends have gone out of bounds, resulting
in a "Hi" appearing on the logged data. In the case
of Figure 4, there were six individual instances where
the residual trends exceeded the threshold value.
5)
Dormancy: depicting a recognisable timeframe
where flow remains consistently low for a prolonged
period of time - a situation that regularly occurs between
the hours of midnight and dawn. Additionally, dormancy
periods have been known to occur during mid-morning
and mid-afternoon at certain micro-flow sites - particularly
during winter.
Following the successful trials, Coliban Water purchased
the Bealiba unit.

Figure 5: Chlorine Residuals
and Flow Rates - Winter Flow
5.0
CONCLUSIONS
This paper describes the results of the trial of a novel
water disinfections system, Smartaflow Chlorisafe, in
a remote community in regional Victoria. The trials
enabled modifications to be made to the unit in order
to cope with particular challenges at the site related
to hydraulic and power requirements and the fluctuating
pH levels in the water. Following these modifications,
the system demonstrated its capability to provide consistent
performance within acceptable chlorine residual ranges.
The system therefore clearly overcomes the challenge
of dosing precise amounts of disinfection agent into
variable, and sometimes near zero flows, often in unfavourable
conditions. The system also overcomes OHS concerns related
to the handling of sodium hypochorite.
The Smartaflow Chlorisafe system offers a solution for
water corporations to be able to meet the challenges
of ADWG compliance, enabling the safe, reliable and
efficient dosing of disinfection at the extremities
of water networks, that is not viable using traditional
technologies.
6.0
REFERENCES
United States Environmental Protection Agency (2001),
"Factoids: Drinking Water and Ground Water Statistics
for 2001". ABS - Census of population and housing.
DOWNLOAD
(pdf
70 KB)
|