|
Conference Papers | 2003 Conference Papers
MANGANESE
REMOVAL USING CHLORINE OXIDATION AND POWDERED ACTIVATED
CARBON
Mark Samblebe, Treatment
Technologist,
North East Water
DOWNLOAD
(pdf
655KB)
ABSTRACT
Draining
of Lake Mulwala in May/June 2002 and persistent low
rainfall in Springhurst caused raw water quality for
the Yarrawonga and Springhurst water supplies to be
adversely affected. Lowering water levels in both dams
lead to elevated concentrations of Manganese (Mn) entering
the treatment plants and reticulation systems. Several
methods of Mn removal reported in literature were tested
and it was found that oxidation of the Mn using Sodium
Hypochlorite with contact times available in the plants
and the addition of Powdered Activated Carbon during
the flocculation stage achieved optimal removal of the
Mn 
Systems
were put in place utilising these findings, which have
proven to consistently reduce raw water Mn concentrations
in excess 0.42mg/L at Yarrawonga and up to 1.2mg/L at
Springhurst to levels well below the guideline value
of 0.1mg/L. Particle counting was also found to be a
sensitive and effective monitoring tool for indicating
Mn breakthrough due to system failures at Springhurst.
1.0
INTRODUCTION
In
early June 2002 the North East Water (NEW) Yarrawonga
Water Treatment Plant (WTP), located on the banks of
Lake Mulwala experienced treatment difficulties due
to changing raw water quality. Operating staff noticed
chlorine residuals were becoming difficult to maintain
despite the apparent cleanliness of the filtered water
prior to chlorine addition. This lead the treatment
plant operators to test for the chemicals Iron (Fe)
and Manganese (Mn) in the raw at treated water supplies
in an effort to find an answer. It was found that Mn
levels up to three times the guideline level of 0.1
mg/L were entering the reticulation system post treatment
and that the raw water levels were between 0.37 and
0.42 mg/L Mn. Not long after, several customer complaints
regarding dirty water and staining of washing were lodged
and a method of removal was under investigation.
These
parameters are not tested on a routine basis at the
plant as it usually draws water from the surface waters
of Lake Mulwala and has had no history of high Mn in
the raw water. At the time of the incident the lake
was drained for routine (once every ten years) maintenance
of the dam wall, leaving available for water only the
slow moving Murray River (reduced to minimal winter
flows) and bare mud flats usually inundated with water.
This led to the significant changes in raw water quality
and treatment plant performance that required immediate
attention.
Several
previously reported methods to remove the Mn were trailed
in laboratory jar tests and a solution involving the
use of oxidation via pre-dosing chlorine and Powdered
Activated Carbon addition during the flocculation stage
was implemented.
Following
this event, no inflow to the Springhurst reservoir for
an extended period led to the slow draining of the Springhurst
Reservoir. Again elevated Manganese concentrations were
observed and a significant 'black water' event followed.
The same method developed during the Yarrawonga incident
was employed with success and the removal of Mn monitored
via a particle counter.
The
following report outlines results obtained from Yarrawonga
laboratory testing, the performance of the recommended
method of Mn removal through the treatment plant, costs
associated with operating the methods on a commercial
scale and the use of particle counting to monitor treated
water manganese concentrations at Springhurst.
2.0
THEORY - BACKGROUND
Why
did the water raw quality at Yarrawonga and Springhurst
change the way it did? The elements known as Iron (Fe)
and Manganese (Mn) are often found naturally in surface
waters used for drinking supplies, and are essential
elements for healthy life. When dissolved in water Mn
and Fe are present in both soluble and insoluble forms.
When Mn and Fe are present in a water body they react
with oxygen (and other oxidants) to become insoluble
in water (i.e. they become solids), when a river course
is dammed and water movement (turbulence) is reduced,
these solids settle from the still water eventually
being deposited on the bottom becoming part of the sediments.
The oxidation of Mn forms a very dark if not black stain
in the water which can then badly stain clothes and
other items around the house.
At
most times this 'sinking' of Mn and Fe to the bottom
of lakes, does not effect a water treatment plant as
these facilities usually draw their water from the upper
region of the water column and many can even vary the
depth of their water off-take to avoid both anaerobic
(oxygen deprived) lower waters contaminated with metals
such as Iron and Manganese or in summer months, avoid
surface waters with high exposure to sunlight which
may experience algae blooms.
When
Lake Mulwala was drained NEW had to extend their off-take
pipes and commission a new floating pontoon for the
raw water pumps in order to compensate for the increased
distance required to reach and pump the water from the
exposed Murray River. It was not foreseen that Mn and
Fe concentrations would increase the way they did, as
there had never been an incident related to high concentrations
reported before. At Springhurst, high concentrations
of Iron had been evident for some time and a removal
system utilising aeration and pH elevation for oxidation
was in place. This system proved to be insufficient
for removal of the Mn concentrations in the raw water.
It was approximately one week after the lake had been
drained to completion that the elevated Mn concentrations
were reported, this was caused by the settling of Mn
and Fe to the bottom of the lake over a long time period,
via the oxidation process described above.
The
problem becomes further compounded by the treatment
process itself, where the oxidant, Chlorine is added
late in the process for disinfection causes remaining
Mn to be precipitated from solution in the clear water
storage and reticulation system. To further add to this,
any un-oxidised Mn still in the system can be oxidised
by detergents used in the home (clothes washing) which
can lead to staining of clothes, sinks and tubs.
In
order to remove Mn from a water supply general theory
to date involve the complete oxidation of the compound
either by aeration or using chemicals such as Chlorine,
Potassium Permanganate, or Hydrogen Peroxide, followed
by flocculation and coagulation of the oxidised solids
liberated. These processes are also known to be improved
by raising the pH of the water to greater than 8.5,
which in itself aids the oxidation process. Several
tests were performed at Yarrawonga using chemicals that
were readily available (Sodium Hypochlorite) and able
to be put in place without any major risk to the staff,
consumers or environment.
All
tests were performed simulating detention times available
in the treatment plant to determine the best option
for removal that could be quickly incorporated into
the system as it stood.
3.0
RESULTS AND DISCUSSION
3.1
Yarrawonga
Table
1 outlines the conditions under which jar tests were
performed based on calculation of detention times throughout
the treatment plant.
Table 1: Flocculation Parameters used Throughout Laboratory
Trials

Optimal
dose rates for Soda Ash and Polyaluminium chlorohydrate
were determined to be 15mg/L soda Ash and 5 mg/L MegaPAC.
These dose rates returned a flocculated water of pH
7.3-7.5 with a solid B-C sized flocc. Throughout the
three days of lab testing further optimisation of the
MegaPAC dose was required and a dose rate of 5.7 mg/L
was deemed optimal.
Sodium
Hypochlorite was dosed to several samples, mixed and
allowed to stand for 27 minutes contact time and residual
Free Cl was measured and recorded. Soda Ash and MegaPAC
were then added at the pre-determined optimal doses.
Results of jar tests performed can be seen in Figure
4.1. It can be seen that a significant relationship
exists between chlorine residual concentration and filtered
water manganese concentrations (Line of best fit, R2
= 0.9391), however no results were found to be below
the guideline limit even with a free chlorine residual
of 2.25mg/L. This method was deemed unsuitable for the
practical application due to the high residual chlorine
levels after settling. It was decided that further tests
would be carried out using Hydrogen Peroxide and Powdered
Activated Carbon.
Figure
1: Residual Manganese vs. Chlorine Residual from jar
tests with and without Powder Activated Carbon Addition
Figure
1 also shows a comparison of results for jar tests where
Powdered Activated Carbon was added. These results show
a difference in Mn removal between those which had PAC
added and those that didn't. Samples where PAC was added
showed much lower Mn residuals than those that did not.
The
results summarised in Figure 1 were analysed for statistical
significance via a 'single factor' (or 'one way') analysis
of variance (ANOVA) to determine the significance of
the differences observed in the two treatments. A P
(probability) value of 2.75´10-5 was obtained
indicating a significant difference in results obtained
from the two treatments (see Table 2).
Table
2: Analysis of variance table comparing samples dosed
with Powdered Activated Carbon with those not dosed
with PAC.

Results
obtained from jar tests that raised pH prior to flocculation
did not indicate effective removal of manganese, nor
was the trend observed significant (Figure 4.2). In
samples where chlorine was added also, an improvement
in Mn removal with raised pH was observed however all
residual Mn concentrations were above the 0.1mg/L guideline
limit.
Figure 2: Manganese residual concentrations V's Pre-Flocculation
pH for samples with and without chlorine addition

From
results obtained Mn removal via pre-dosing Sodium Hypochlorite
followed by Powder Activated Carbon addition was put
into place utilising materials the Authority had available
at other sites. Close monitoring of the process over
the following two weeks showed a gradual decrease in
treated water manganese concentrations over the first
day of operation followed by consistent readings well
below the guideline value (Figure 3).
Treated water manganese concentrations since two days
after the installation of the system have averaged 0.014mg/L
Mn, ranging from 0.000 to 0.034 mg/L Mn.
Figure
3: Manganese residuals throughout the Yarrawonga Water
Treatment Plant (6/6/02 - 21/6/02).

It
can also be seen in Figure 3 that the Manganese concentration
in the raw water began to decline on the 15th June reaching
0.17mg/L Mn on the 21st June. This trend was caused
by rainfall upstream in the catchment that assisted
in flushing the manganese from the raw water supply.
The upper catchment rainfall event also increased raw
water turbidity as can be seen in Figures 4 and 5 reaching
a maximum turbidity of 68.1 NTU. Alterations to all
chemical doses were required in order to maintain adequate
flocculation and effective Mn removal.
Figure
4: Turbidity - Raw, settled and filtered water samples
from Yarrawonga WTP.

Figure
5: Raw water Turbidity and Manganese concentrations
at the Yarrawonga Water Treatment plant from 8/6/02
to 21/6/02.

3.2
Springhurst Particle Count Monitoring
Figure
6 shows the particle count trend for the treated water
over one month at Springhurst. Several spikes can be
seen where particle count increased significantly especially
over the first week or two. These spikes were observed
when a part of the system failed. When either the chlorine
or the PAC pumping system failed Mn breakthrough was
observed, and the breakthrough was monitored via the
particle counter. When Mn concentrations were below
0.02mg/L particle count averaged around 400-800 particles/100ml
and an increase from 0.02to 0.1mg/L resulted in particle
counts up to 90,000 particles/100ml. Turbidity tracking
was found to be less sensitive with Mn breakthrough
tracking where increases in the range from 0.3ntu to
4ntu were seen at a maximum (Figure 7).
Figure
6: Treated water particle count over time at Springhurst
WTP

Figure 7: Treated Water Turbidity over time at the Springhurst
WTP

4.0
COST OF TREATMENT
Throughout
the duration of the exercise the extra cost of treatment
has been as summarised in table 3 below. It can be seen
that both increased costs via using chemicals not usually
applied at the site and savings have occurred via reduced
consumption of chemicals usually used.
Table
3: Additional cost of production ($/KL) for the manganese
removal system compared to usual cost of Production.
(un-shaded cells are based on normal operating parameters,
shaded cells represent current dosing costs).

It
can be seen in table 3 that the additional expense of
the manganese removal exercise was 1.84 cents per kL
(total cost 3.5 cents/kL), which doesn't seem significant
until compared to the original cost of treatment which
was 1.73 cents/kL, this represents a doubling in the
chemical cost involved in treatment.
The
main contributing factor to this increase was the large
quantities of Sodium Hypochlorite required to achieve
adequate Mn removal, although the process that has been
developed can be optimised somewhat to reduce this expense,
as the time available for development and commissioning
of the method was limited. It can also be noted that
the additional cost of treatment derived from the PACl
dosing is almost equally offset by the reduced need
for pH correction that this flocculant allows where
the cost of PACl was $180.13 more than the regular expense
of Alum, however with no requirement for Soda Ash once
river flows increased and raw water pH followed, only
an additional $43.53 was required.
5.0 CONCLUSIONS
In
conclusion the test work performed lead to NEW achieving
high removal rates of Manganese via the addition of
Chlorine and Powdered Activated Carbon. The cost of
the new treatment method was found to be greater than
regular modes of treatment however several benefits
to the authority have been found throughout the investigation.
These include what is so far an un-reported method of
Mn removal which utilises PAC, the elimination of customer
complaints regarding dirty water or staining of washing
in Yarrawonga and the installation of the PAC dosing
facility which can be utilised during summer months
when taste and odour issues are often a cause for concern
due to algae blooms.
At
Springhurst the system developed at Yarrawonga once
again proved efficient with removing high levels of
manganese and particle counting is also seen as a monitoring
tool with plenty of potential in manganese affected
water supplies. It is recommended from the findings
of this report that more work be done to properly refine
(or 'optimise') the process which could deliver a more
efficient chemical dosing regime as methods utilised
throughout this event focused on those which could be
very quickly and easily incorporated into the treatment
process as it stood and was limited by several factors.
The system was installed as a 'temporary' item.
DOWNLOAD
(pdf
655KB)
|