|
Conference Papers | 2001 Conference Papers KNOW
YOUR FILTERS
Sandy McGregor -
Water Treatment Technologist,
Gippsland Water
DOWNLOAD
(pdf
416K)
ABSTRACT
This
paper provides engineers and operators with helpful
information for the identification and remediation of
poor filter performance, based on experience gained
by Gippsland Water in filter management. The following
points are covered:
| » |
The
importance of well operated and maintained filters. |
| » |
Operator's
knowledge of filter performance. |
| » |
Observations
from failures and their reasons. |
| » |
Rebuilds, modifications and simple remedies. |
| » |
Re-establishment
of performance and ongoing monitoring. |
| » |
Performance
monitoring tools. |
KEY
WORDS
Filter;
Performance; Failures; Operator; Modifications; Turbidity
1.0
INTRODUCTION
Gippsland Water has adopted the Hazard Analysis And
Critical Control Point (HACCP) management philosophy
for the operation of its filtration plants. Under HACCP
the filters in a treatment plant are considered to be
a critical control point.
As it is the filter that provides the physical barrier
to pathogens in the treatment process it is necessary
to ensure that they are in top operating condition at
all times. To monitor and assess this, improvements
in on-line instrumentation and physical assessments
/ inspections have been a main focus over the last four
years.
Gippsland
Water has made progress in this area and now actively
monitors the performance of its filtration plants and
encourages its operators to look at the operation of
their plants and perform some of the work discussed
in this paper themselves. It is from this work that
much of the information in the following discussion
is derived.
Note:
Due to the variety of filter types and designs the information
given is a guideline only.
2.0 DISCUSSION
2.1
Normal operation
A typical water treatment plant filter operated under
normal conditions should produce filtered water with
a turbidity of less than 1 NTU most of the time, with
an average of less than 0.5 NTU being desirable. Well-operated
treatment plants with properly maintained filters can
produce filtered water of less than 0.05 NTU when operated
at optimum.
Backwashing frequency of 8 to 96 hours are common. In
general, if turbidity breakthrough occurs in less than
8 hours, questions relating to the economy of plant
performance need to be addressed. Excessive filter run
durations are not encouraged as the risk of taste and
odours due to anaerobic floc increases. For example,
filter runs greater than 96 hours.
Head
loss build up during a filter run is expected see figure
1 for an example of a typical filter run detailing the
increase in head loss and the changes in turbidity.
Typically two meters is used as the trigger level for
a backwash. However it is suggested that total filter
bed depth be used as the head loss set point.
Values
greater than two meters lead to more rapid head loss
increases, which can become unsustainable. Unsustainable
head losses result in blinding off of filter. Allowing
this to happen frequently will compromise the backwash
regime as the filter becomes more difficult to clean.
(Refer to Figure 1:)
Figure
1: Turbidity & Head loss over Time (Water Training Centre)

2.2
Filter performance criteria
Filter performance criteria is a benchmark for monitoring
the performance of your filter/s. Table 1 is an example
of the filter performance criteria used by Gippsland
Water.
Table 1: Typical filter performance
criteria values

The
performance trial should take at least two weeks or
longer. During the trial the filter should be subjected
to varying conditions, both high and low solids loading,
flow rates and extended filter runs. Solids loading
trials and be carried out by changing the off take at
the supply reservoir or by changing the conditions of
upstream process such as the clarifier operation.
During
the trials the filter should be monitored for the following:
| » |
Inlet
& Outlet turbidity and particle counts. |
| » |
Head
loss (or outlet valve position) and Water Level. |
| » |
Backwash
waste stream Turbidity and adequate backwash duration. |
| » |
Residual
Coagulant and Chlorine demand. |
| » |
Residual
Iron, Manganese and Organic Carbon. |
| » |
Measured
filtration rate and Backwash rate. |
When trended or graphed this data can be used to determine
the operational limits of the filter as well as providing
the baseline data for future reference, and can indicate
deterioration of the filter performance. (The graph
becomes a control chart)
2.3
Assessment of filter state & condition
Good filter performance and condition monitoring returns
benefits in the form of early detection of potential
causes for filter failure. It can also be sed that where
a filter has failed due to an operational practice,
it is also common to find poor filter monitoring. But
this is not always the case.
Performance
monitoring tools such as on-line instruments and data
trending is the first point of call. Trends or graphs
of data such as filtrate turbidity and head loss enable
changes in performance to be seen over very long periods.
Additional information such as the filter inlet turbidity,
backwash waste stream turbidity, filtration rates and
particle count data all enable better filter management.
In
addition to on-line instrumentation, periodic physical
inspections of filters and observing the backwashes
are important. Since 1997, Gippsland Water has carried
out assessments and inspections of most of its filters.
These assessments have led to filter refurbishments,
modification work, and supplementary on-line instrumentation
at some sites.
A typical performance inspection would involve the following.
| » |
Searching
records and checking plant for design data. |
| » |
Observing
the backwash routine. |
| » |
Physically
inspecting the media. |
| » |
Taking
media samples for shake testing. |
| » |
Documenting findings and reporting results including
recommendations. |
By observing the backwash it is possible to determine
how healthy the filter is. Two of the most useful observations
during a backwash are the level of bed fluidity of the
media, and air scour pattern. Both of these observations
tell us information about the condition of the filter
bed. The fluidity can be determined by a long handled
(4 metres) probe, with a surface area of approximately
75cm square at the end. The resistance to the probe
being lowered into the filter indicates the amount of
fluidity. If the probe has to be pushed in to the media
then the backwash rate can be considered as inadequate
or localised clogging of the bed has occurred. Further
physical inspection may be required. Media boiling during
the wash phase indicates that the support media has
been irreversibly disturbed. The degree of boiling will
indicate the extent of the failure and will indicate
if the bed needs to be replaced.
In consistency of the air scour pattern, say large volcano
type patches or very still areas can also indicate problems
with the support media or problems with the under drain
pipe work. See figures 8 & 9. Broken pips or cracking
of the filter bed are also causes for backwash problems.
The physical inspection of the media is carried out
by scratching around and feeling the media. In doing
this you are able to detect foreign matter, media cracking,
and support media on the surface. You are also able
to get a rough estimation of the media cleanliness and
presence of mud balls, (Refer Figures 2 to 6). Figures
4, 6 & 8 are examples of foreign matter trapped in the
filter bed.
Do not attempt to carry out any filter entry with
out adequate safety equipment and supervision, as most
filters are confined spaces.
| Figure
2: Uneven media surface, as a result of the filter
inlet design |
|
Figure
3: A 50mm Sludge layer that clearly shows cracking
and shrinkage |
 |
|
 |
|
|
|
| Figure
4: Rubbish removed from within the filter during
refurbishment at Morwell |
|
Figure
5: Mud ball found in a filter that had completely
failed at Traralgon |
 |
|
 |
| |
|
|
| Figure
6: Rubbish removed from within the filter during
refurbishment at Sale |
|
Figure
7: An example of a shake test. Layers of media,
sludge and water can clearly be seen |
 |
|
 |
The
shake test is a simple procedure that can be completed
by anyone, and is done to indicate the effectiveness
of the backwash. The shake test is done after a backwash
and is carried out be taking a 500ml core sample from
various locations and depths from the filter. Vigorously
shake the sample in one litre of water and allow to
stand for 20 minutes, then determine the percentage
of settled sludge versus the volume of media. If the
result of the test is greater than 15% sludge, then
the backwash regime should be reconsidered as this indicates
poor backwashing. Values less than 8% are considered
normal. (Refer Figure 7).
Generally failures can be attributed to problems with,
the design, the construction, or operation of the filter.
Design failures are difficult to overcome, as they are
often an integral part of the filter structure. See
Figure 2 for example. Construction failures generally
relate to the way in which the media bed is laid. These
failures often become evident as sink holes in the media
or boiling during backwashes. In most cases the filter
bed needs to be replaced, with the possibility of some
underdrain work. Operational failures are probably the
most common type and are often represented by blinding
of the media, mud ball formation, and high filtrate
turbidity during the filter run. (Refer Figures 3, 5
& 10) Figure 10 was the result of an underdrain failure,
which affected the performance of the other filters
at the plant.
These failures may require minor or major work to rectify.
Chemical washing, physical removal of the offending
material, or possible total replacement of some or all
of the filter media may be required.
| Figure
8: Support
gravel has been completely displaced. A still area
in the air scour pattern was the first indication
|
|
Figure
9: A
plastic bag covering an under drain nozzle
|
 |
|
 |
| |
|
|
| Figure
10: Result of a broken under drain nozzle. Sand
entered the backwash tank and was redistributed
to other filters. This required significant work
to remove the sand and resulted in other filter
rebuilds. |
|
Figure
11: Typical of a good air scour pattern during testing |
 |
|
 |
2.4
Remedial action
Modifications and simple remedies are the most common
approaches to fixing filter problems. As in the example
described below the remedial action to overcome the
failure was simple. However, it may not always be so
easy.
In the case of a polymer over dose, the filter media
may be blinded off to the point that it is necessary
to chemically clean the filter by washing it with highly
concentrated solutions of caustic, hypo, acid or other
chemicals such as detergents. Regained performances
can range from 60 to 100% of original design, depending
on the situation. The drawback is that large quantities
of contaminated water are left for disposal. Chemical
cleaning of the filter media can also be used to eliminate
lime build up where lime is used as a coagulant for
the removal of iron, manganese or chemical binding by
calcium and for treatment of algal build ups.
Practical example of remedial action.
An automated treatment plant built in southern NSW,
was designed with data from seven years of dry wether.
The plant was commissioned with a backwash routine adequate
for the plant loading under dry conditions. As time
progressed the through put was increased due to demand
and the weather became wet again.
As
a result the filter was running at above design rates
and the raw water quality changed. The plant's chemical
dosing system was programmed to cope with this, but
the backwash routine remained unchanged. As a result
the filter was not backwashing as efficiently as it
should have and eventually caused turbidity breakthrough
and finally blinding of the media. Action was taken
to rectify this by consecutive backwashes until the
filter was considered to be clean again. The backwash
was reassessed and optimised to handle the new operating
conditions of the plant.
2.5
Rebuilds & modifications
Rebuilds are often a last resort as the cost of this
work can be very high. Other remedial action that can
be taken to prevent filter failures is the replacement
of media and modification of the way in which the filter
operates.
For example- At the Mirboo North Water Treatment Plant
an air scour system and backwash pump VSD were installed.
This was done to improve the backwashing of the filter.
The installation of a blower meant that air scouring
could now be employed. The installation of the VSD allowed
controlled ramping of the wash water rate. Controlled
ramping of the wash water removed the risk of the support
media being disturbed due to sudden surges of water.
The modification has also enabled the use of combined
air scour and water backwashing.
At
the Heyfield Water Treatment Plant it was noticed that
during the filter run turbidity spikes occurred. This
was investigated using a particle counter. The turbidity
spikes were attributed to valve operation. For example,
when the plant started a backwash the filter outlet
valves would open to about 80% to allow the filter to
drain. This increased the flow through the filter to
a point that allowed turbidity break through. This was
rectified by restricting the valve operation to only
open to approximately 10% above the last operating position.
The reduced valve movement slowed the flow through the
filter and stopped the turbidity spike. The investigation
also found that when the filter was put back on line
the ripening duration was extreme. It was found that
the filter level control loop was not correctly tuned,
which resulted in the filter outlet valve swinging wildly
while trying to maintain level set point. To rectify
this the valve operation was slowed and the control
loop re-tuned. The result was a much-improved level
of control and a reduction of the turbidity and particle
counts exiting the filter. A commonly neglected but
very important functional check, which can prevent filter
failure is the Air Scour test.
This
test is carried out before adding the filter media on
an empty filter with approximately 150mm of water in
the bottom and the air blower running. This test gives
a clear indication of the distribution of the air pattern.
If the air distribution is not correct the filter will
not backwash correctly. This will lead to long-term
degradation in performance. (Ref Fig 11)
2.6
Re-establishment of performance criteria.
After a filter has been modified or rebuilt, it is good
practice to re-determine its performance. This will
provide new reference data for comparison in the future.
A performance trial is also used to verify the effectiveness
of a modification.
3.0
CONCLUSION
The importance of well-operated and maintained filters
is essential, as a filter that is in poor operational
condition or is being operated poorly, increases the
chance of compromising the quality of the product water
delivered to our customers.
The
operator's knowledge of filter performance and how to
monitor and improve it is important too, as most of
the time it is the operator who is responsible for the
operation and maintenance of his / her site. It is also
the operator who has to determine what is happening
when the plant performance is not up to scratch and
what to do about it. "And as we all know, this often
happens when we least need problems." Therefore
it is important that he / she has a good understanding
of the water treatment process and has an inquisitive
nature that draws them to observe their plant closely.
References and design texts are ideal for gaining additional
knowledge. Some useful texts are listed under 'References'.
However it is the "getting your hands dirty" experience
that reinforces the text book knowledge, as you get
to see aspects of filtration and plant performance required
to ensure that plants are running at their optimum.
The
monitoring of filter performance and integrity may not
bring dividends in the short term, but will enable you
to avoid water quality and health incidents. It will
also keep your plant ahead of the changing and more
stringent regulations of the future.
4.0
ACKNOWLEDGMENTS
The
author wishes to thank Dr Peter Mosse for actively encouraging
the preparation of this manuscript, Ms Michelle Colwell
for reviewing the manuscript and Gippsland Water Treatment
Plant operators for their patience during filter assessments
and refreshments.
5.0
REFERENCES
Kawamura, S; 1991; Integrated design of water treatment
facilities; A Wiley-Interscience Publication
Faust,
S D; Aly, O M; Chemistry of water treatment Second
Edition; Ann Arbor Press
Mc
Clellan; 1998; Royal Commission inquiry into the
Sydney Cryptosperidium event.
NHMRC and ARMACANZ; 1996; Australian Drinking Water
Guidelines; Commonwealth of Australia.
Murray,
B.A; 1995; Particle counting in water treatment;
Water, 22 : 37 - 40
Certificate
in water operations stream studies; March 1992; Filtration
subject code CW.13; Water Training Centre > DOWNLOAD
(pdf
416K)
|